IO-Link HubUR-DS Series
IO-Link device that connects multiple standard sensors
and actuators to an IO-Link Master. (IO-Link Hub)
- IO-Link Hub connecting to an IO-Link Master, supporting Digital I/O, Analog I/O, and Temperature inputs
- IO-Link Hubs that can support Digital Inputs or Outputs up to 256 points (16 channels x 16 points)
*When connected to the OPTEX FA UR Series. - By connecting to an IO-Link Master, various I/O functions can be expanded.
This distributed configuration contributes to space-saving, reduced wiring, and improved noise resistance. - A new IO-Link Hub supporting RTD input is now available.
It allows temperature measurement using pt100 RTD sensors, with data transmitted and monitored via IO-Link communication. 



Lineup
| Type | Shape | Model | |
|---|---|---|---|
| IO-Link Hub Digital I/O |
16-input | ![]() |
UR-DS16D |
| 16-output | ![]() |
UR-DS16T | |
| 8-input, 8-output | ![]() |
UR-DS8D8T | |
| IO-Link Hub Analog I/O |
4-input | ![]() |
UR-DS4DA |
| 4-output | ![]() |
UR-DS4DA | |
| IO-Link Hub Temperature RTD |
8-input | ![]() |
UR-DS8RTD |
Specifications
Model Specifications IO-Link Hub, Digital I/O
| Model | UR-DS16D | UR-DS16T | UR-DS8D8T | |||
|---|---|---|---|---|---|---|
| Communication interface | IO-Link (Operates as a device) |
IO-Link (Operates as a device) |
IO-Link (Operates as a device) |
|||
| Number of process input data byte | 2 bytes | 2 bytes | 2 bytes | |||
| Number of process output data byte | 1 byte | 4 bytes | 3 bytes | |||
| Minimum cycle time | COM3 | 0.4 ms | 0.6 ms | 0.5 ms | ||
| COM2 | 2.4 ms | 3.6 ms | 3.0 ms | |||
| IO-Link revision | 1.1 | 1.1 | 1.1 | |||
| Communication speed | COM3 (230.4 kbps)/COM2 (38.4 kbps) Switching by service data. (default value: COM3) |
|||||
| Power supply for communication functions | Power supply for IO-Link | Output power supply | Power supply for IO-Link | |||
| Input Specifications | ||||||
| Number of input points | 16 points | - | 8 points | |||
| Input related | Batch source(PNP) / sink(NPN) input switching method (default: switch by process output data) | Batch source(PNP) / sink(NPN) input switching method (default: switch by process output data) | ||||
| Withstand voltage | From I/O terminal batch to IO-Link batch 500 VAC for 1 minute |
From I/O terminal batch to IO-Link batch 500 VAC for 1 minute |
||||
| Insulation resistance | From I/O terminal batch to IO-Link batch 500 VDC 10 M ohm or more with an insulation resistance tester |
From I/O terminal batch to IO-Link batch 500 VDC 10 M ohm or more with an insulation resistance tester |
||||
| Input / Output common | 16 points common | 8 points common | ||||
| Rated input voltage | 24 VDC Ripple (P-P) incl. 5 %. | 24 VDC Ripple (P-P) incl. 5 %. | ||||
| Rated input current (typical) | 4.9 mA | 4.9 mA | ||||
| Insulation method | Photocoupler Isolation | Photocoupler Isolation | ||||
| Maximum number of simultaneous input points | 100 % simultaneous ON | 100 % simultaneous ON | ||||
| Voltage and current at ON | 15 VDC or higher / 3.0 mA or higher | 15 VDC or higher / 3.0 mA or higher | ||||
| Voltage and current at OFF | 8 VDC or less / 1.5 or less | 8 VDC or less / 1.5 or less | ||||
| Input resistance | 4.7 k ohm | 4.7 k ohm | ||||
| Input response time | 0 to 200 ms (1ms unit, default: 10 ms) |
0 to 200 ms (1ms unit, default: 10 ms) |
||||
| Output Specifications | Standard output | High current output | Standard output | High current output | ||
| Number of output points | - | 16 points | 8 points | |||
| High current output function | Supported by output C to F source(PNP) | Supported by output C to F source(PNP) | ||||
| Rated load voltage | 12 VDC/24 VDC (Allowable voltage range 10.2 to 28.8 VDC) |
12 VDC/24 VDC (Allowable voltage range 10.2 to 28.8 VDC) |
||||
| Maximum output load current | 0.5 A per 1 point |
4 A per 1 point |
0.5 A per 1 point |
4 A per 1 point | ||
| Maximum total output load current | 12 A | 12 A | ||||
| Maximum inrush current | 0.6 A | 6 A | 0.6 A | 6 A | ||
| Output residual voltage at ON | 1.2 V or less | 0.4 V or less | 1.2 V or less | 0.4 V or less | ||
| OFF output leakage current | 0.1 mA or less | 0.1 mA or less | ||||
| Output response time | 0.2 ms or less (OFF to ON) 1.5 ms or less (ON to OFF) |
0.2 ms or less (OFF to ON) 1.5 ms or less (ON to OFF) |
||||
| Surge suppressor | Zener diode | Zener diode | ||||
| I/O power supply voltage | 12 VDC/24 VDC (Allowable voltage range 10.2 to 28.8 VDC) |
12 VDC/24 VDC (Allowable voltage range 10.2 to 28.8 VDC) |
||||
| I/O power supply current consumption | 55 mA max (at 24 VDC) | 55 mA max (at 24 VDC) | ||||
| Output related | Source(PNP) / Sink(NPN) switching for each output individually |
Source(PNP) / Sink(NPN) switching for each output individually |
||||
| Output reverse voltage protection | Protected | Unprotected | Protected | Unprotected | ||
| Common (output) | 16 points individually switchable common | 8 points individually switchable common | ||||
Model Specifications IO-Link Hub, Analog I/O
| Model | UR-DS4AD | UR-DS4DA |
|---|---|---|
| Communication interface | IO-Link (Operates as a device) | IO-Link (Operates as a device) |
| Number of process input data byte | 8 bytes | 8 bytes |
| Number of process output data byte | 1 byte | 1 byte |
| Minimum cycle time | 0.7 ms | 0.7 ms |
| IO-Link revision | 1.1 | 1.1 |
| Communication speed | COM3 (230.4 kbps) | COM3 (230.4 kbps) |
| Power supply for communication functions | Power supply for IO-Link | Power supply for IO-Link |
| Input Specifications | ||
| Number of input chanels | 4 CH | - |
| Input related | Voltage (0 to 10 V, -10 to 10 V, 0 to 5 V, 1 to 5 V) / Crrent (0 to 20 mA, 4 to 20 mA) Input switching method (default: switched by process output data) |
|
| Withstand voltage | 500 VAC for one minute between analog input batch and IO-Link batch | |
| Insulation resistance | 10 M ohm or higher between analog input batch and IO-Link batch at 500 VDC | |
| Interchannel isolation | None (common) | |
| Max. input voltage | ±11 V | |
| Max. input current | 24 mA | |
| Insulation method | Photocoupler Isolation | |
| Voltage input impedance | 250.5 k ohm | |
| Current input impedance | 246 ohm | |
| Voltage Accuracy | ±0.30 % of F.S. (ambient temperature at 25 °C )*1 Temperature coefficient (typical example): ±80 ppm/°C (0.008 %/°C) |
|
| Current Accuracy | ±0.30 % of F.S. (ambient temperature at 25 °C ) Temperature coefficient (typical example): ±110 ppm/°C (0.011 %/°C) |
|
| Input resolution | 16 bit | |
| Output Specifications | ||
| Number of output chanels | - | 4 CH |
| Output related | Voltage (0 to 10 V, -10 to 10 V, 0 to 5 V) / Crrent (0 to 20 mA) Output switching method (default: switched by process output data) |
|
| Withstand voltage | 500 VAC for one minute between I/O terminal batch and IO-Link batch | |
| Insulation resistance | 10 M ohm or higher between all I/O terminals and IO-Link terminals at 500 VDC | |
| Inter-channel isolation | None (common) | |
| Max. output voltage | ±11 V | |
| Max. output current | 24 mA | |
| Insulation method | Photocoupler Isolation | |
| Voltage output equivalent impedance | 0.3 ohm | |
| Voltage Accuracy | ±0.2 % of F.S. (ambient temperature at 25 °C)*1 temperature coefficient (typical example): ±80 ppm/°C (0.008 %/°C) |
|
| Current Accuracy | ±0.2 % of F.S. (ambient temperature at 25 °C) temperature coefficient (typical example): ±10 ppm/°C (0.001 %/°C) |
|
| Output resolution | 16 bits |
*1. Accuracy when input type is set to 0 to 10 V or -10 to 10 V.
Full scale is calculated as 10 V even when 0 to 5 V or 1 to 5 V is set.
Model Specifications IO-Link Hub, Temperature RTD 8-input
| Model | UR-DS8RTD |
|---|---|
| Communication interface | IO-Link (operates as device) |
| Number of process input data byte | 16 bytes |
| Number of process output data byte | 1 byte |
| Minimum cycle time | 1.2 ms |
| IO-Link revision | 1.1.3 |
| Communication speed | COM3 (230.4 kbps)/COM2 (38.4 kbps) Switching by service data. (Default value: COM3) |
| Power supply for communication functions | IO-Link power supply |
| Input Specifications | |
| Number of input chanels | 8 channels |
| Compatible resistance thermometer | Pt100, 3-wire type |
| Maximum input current | Approx. 1 mA (When measured at 25°C) |
| Measurement range | -200 to +1,000 °C |
| Accuracy | -200 to -60°C: ± 1.0°C -60 to +300°C: ± 0.3°C +300 to +600°C: ± 1.0°C +600 to +1,000°C: ± 2.0°C (at ambient temperature of 25°C) |
| Temperature characteristics | ±50 ppm/°C (Within the ambient temperature range) |
| Resolution | 16 bits |
| Dielectric withstand voltage | 500 VAC for one minute between platinum resistance thermometer input terminal batch and IO-Link batch. |
| Insulation resistance | 10 Mega ohm between platinum resistance thermometer input terminal and IO-Link terminals at 500 VDC |
| Inter-channel isolation | None (common) |
| Insulation method | Photocoupler, transformer insulation |
| Sampling cycle | 2 ms |
IO-Link Hub General Specifications
| Item | Specifications | |
|---|---|---|
| Power supply voltage | 24 VDC ±15 % (SELV and LIM power supplies or UL1310 Class 2 power supplies)*1 |
|
| Current consumption | 50 mA max. (for 24 VDC*2) | |
| Operating temp. | 0 to +55 °C (no freezing) | |
| Operating humidity | 5 to 95 % RH (no condensation) | |
| Storage temp. | -25 to +75 °C (no freezing) | |
| Storage humidity | 5 to 95 % RH (no condensation) | |
| Vibration resistance | IEC 61131-2 compliant |
|
| Shock resistance | IEC 61131-2 compliant Peak Acceleration: 150 m/s2 (15 G), 3 directions in each of the X,Y and Z directions, 3 times each (total 18 times) |
|
| Atmosphere | No corrosive gas | |
| Operating altitude | 0 to 2000 m | |
| Installation location | Indoor use | |
| Degree of protection | IP20 (Not UL Certified) | |
| Overvoltage category | II or less | |
| Pollution degree | 2 or less | |
| Device class | Class Ⅰ | |
| Applicable regulations | EMC | EMC Directive (2014/30/EU) |
| Environment | RoHS Directive (2011/65/EU), China RoHS (MIIT Order No.32) | |
| Applicable standard | EN 61131-2*3 | |
| NRTL certification | Planned | |
| Company standards | Noise resistance: Feilen Level 3 cleared | |
| Compatible DIN rail | TH35-7.5Fe, TH35-7.5Al | |
| Compatible wire | Power terminal block: AWG 24 to 12 I/O terminal block: AWG 28 to 16*4 |
|
| Material | Housing: PC, Keys and DIN rail mounting hook: POM,Terminal block: PA | |
| Weight | Approx. 115 g*5 (including terminal blocks, when not wired) | |
| Included accessories | Instruction manual*6, 3 x I/O terminal blocks*7, 1 x Power terminal block | |
*1. Use a Class 2 power supply or a power supply compliantwith SELV (Safety Extra-Low Voltage) circuit and LIM (LimitedEnergy Circuit) circuit standards.
*2. UR-DS4DA not include analog output
*3. Zone A for UR-DS4AD/4DA
*4. Platinum resistance thermometer input terminal block (UR-DS8RTD) AWG 24 to 18
*5. UR-DS4AD weighs approx. 105 g, UR-DS4DA weighs approx. 95 g
*6. UR-DS8RTD Instruction manual only
*7. UR-DS4AD 2 x I/O terminal blocks, UR-DS4DA 1 x I/O terminal blocks